HE 5421 Regulator różnicy ciśnień

- Measuring range 0... 25 / 30 / 40 / 50 / 70 / 100 / 250 / 500 mbar
- 3½-digit display of the differential pressure
- Analog output 0(4)... 20 mA / 0... 10 V
- 2 relay switching outputs (ΔP cleaning and ΔP alarm)
- Display of the switching status of the relays
- Adjustments: switching thresholds for cleaning start, cleaning stop and alarm
- Mains supply: 230 AC; 115 V AC; 24 V AC / DC universal supply
- Explosion protection: Ex II 3D T60°C IP65, approved for Ex-zone 22
- Makrolon housing, 122 x 120 x 55 mm, IP65
The HE 5421 is a universal measuring transducer especially for small differential pressures (< 100 mbar). The actual differential pressure is indicated digitally with 3½-digits. The device has two switching thresholds for monitoring and control purposes, e.g. for the ΔP-dependent dedusting in industrial dust extraction technology. An additional threshold is used for monitoring a maximum differential pressure. The switching state of the relays is indicated with LEDs. The device is dust-proof and approved for operation in explosion zone 22