HE 5421 Regulator różnicy ciśnień

 

  • Measuring range 0... 25 / 30 / 40 / 50 / 70 / 100 / 250 / 500 mbar
  • 3½-digit display of the differential pressure
  • Analog output 0(4)... 20 mA / 0... 10 V
  • 2 relay switching outputs (ΔP cleaning and ΔP alarm)
  • Display of the switching status of the relays
  • Adjustments:  switching thresholds for cleaning start, cleaning stop and alarm
  • Mains supply:  230 AC;  115 V AC; 24 V AC / DC universal supply
  • Explosion protection: Ex II 3D T60°C IP65, approved for Ex-zone 22
  • Makrolon housing, 122 x 120 x 55 mm, IP65

The HE 5421 is a universal measuring transducer especially for small differential pressures (< 100 mbar). The actual differential pressure is indicated digitally with 3½-digits. The device has two switching thresholds for monitoring and control purposes, e.g. for the ΔP-dependent dedusting in industrial dust extraction technology. An additional threshold is used for monitoring a maximum differential pressure. The switching state of the relays is indicated with LEDs. The device is dust-proof and approved for operation in explosion zone 22

HE5421-innen.jpg
he5421-option-e.jpg

Pliki do pobrania:


Do you have questions about this product?
Send us your question - we will answer it immediately.

x

Nasza witryna używa plików cookies i podobnych technologii m.in. w celach: świadczenia usług, statystyk i reklamy.
Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Państwa urządzeniu końcowym.